Reactors and Coils

 

Reactors & Coils

 

Liquid immersed


Rating power: up to 30/50 Mvar

Insulating level: up to LI 750 kV


Accessories

 

 

Reactor

Dry type


Rating power: up to 15 Mvar

Insulating level: up to LI 200 kV


Accessories

 


SEA has designed a wide range of reactors fits for any kind of application required and are available both in the three phase or single phase version, dry type (with cast resin or air insulated MV windings) or liquid immersed type.

Below the main types produced:

Petersen_coil_regulated_by_steps

 

Petersen coils regulated by steps
(with off voltage tap changer)

Single phase reactors with or without magnetic core, connected between a neutral point and ground in MV distribution network.
They are designed to be resonant with network capacitance, limiting earth fault current.
In this type the value of the reactance and the compensation current are the main factor for design.
They can be designed also for a range min/max fault current, selected by a tap changer.

 


      

Petersen coils stepless
(regulated by motordrive)

Reactor connected between the neutral of a power system and ground to compensate (resonant) the capacitive earth fault current.
They are designed to be tuned with network capacitance, limiting earth fault current. In this case change of reactance is continuously adjustable in the prescribed min/max range by motordrive.
Regulation of the compensation current can be made manually or automatically by dedicated control equipment installed in the substation control room.

 


Shunt Reactor        

Shunt reactors

Fixed type

Reactor installed in three-phase networks to increase power factor during off-load or reduced load conditions, reducing losses in the transmission lines (capacitive).
Typically it is installed in the wind farms where variation of the load factor is extended.
It has a fixed rating, connecting to the power line all the time (it can be switched on/off depending on the load).

 

Variable type (VSR)

They are used to stabilize voltage during load variations in the network system. Power rating is not fixed but can be changed in steps ensuring a more stability of voltage and compensating reactive power when the value of load is changed. 

 


Earthing transformers (neutral couplers)

Three-phase unit supplied in power system to provide a neutral connection for earthing purposes, directly or through an impedance.
It can be equipped with an auxiliary LV winding to supply auxiliary loads at the substations.

 


 

 

Air_insulated_Current_limiting_reactor

 

Series reactors

Current limiting reactors

They are series reactors that reduce the short circuit currents in the power system. 
The advantage of their use is that the circuit breakers in the network systems with lower circuit breaking capacity are less expensive.
Another use is reducing inrush current in the motors.
Dry type are used as alternative to the oil filled type and when there is enough surrounding space to keep magnetic field limits below maximum limits permitted by laws and regulations.
Another restriction in selecting oil or dry type reactors are the polluted conditions, critical at the highest levels.
Phases coils can be arranged as three-phase or single-phase units.

 

Neutral earthing reactors

They are single phase units used to ground neutral terminals in MV networks, directly or by impedance.
They can be realized both dry type and liquid filled.

 


Reactors for special applications

SEA can design reactors for special applications like:

  • Filter (tuning) reactors
    They are series connected or parallel connected with capacitors to reduce or block harmonics or control signals with frequences up to 10 kHz. Tipically they are dry type.

  • Damping reactors
    They are series connected with shunt capacitors to limit transient peaks during switching on/off.

  • Smoothing reactors
    Reactors used to reduce/eliminate harmonics within prescribed limits, after AC/DC converters.

  • Furnace reactors
    They are limiting reactors installed in furnace industry to limit short circuit currents.

  • Harmonic filtering reactors
    Used in high harmonic circuits to suppress or limit specific harmonics within specified level.

  • Power factor correction reactors
    Used to increase power factor in all conditions of loads, saving in trasmission losses.